Customization: | Available |
---|---|
Application: | Construction, Underground, Power Station |
Voltage: | Low and Medium Voltage Cable |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Phase Conductor : Aluminium Conductor
Neutral Conductor : AAC/AAAC/ACSR
Insulation : XLPE/PE
Rated Voltage : 1-35KV
Cores : 1,3 Cores
Other Standards: ASTM/NFC 33-209/BS 7870-5/IEC 60502/AS/NZS or according to your requirement.
Application: The aerial bundled cables designed for overhead distribution lines have all conductors made of aluminium,
insulated with XLPE.Phase and neutral cores are laid up in a bundle with a left hand lay. Can be used for fixed installation
as overhead power lines up to 35KV.
![]() |
![]() |
No of cores x cross section
|
Nominal conductor diameter
|
Nominal insulation thickness
|
Nominal sheath thickness
|
AAAC/1120 support conductor size
|
Nominal overall dia
|
Weight
|
Continuous current rating
|
2m/s wind
|
|||||||
mm^2
|
mm
|
mm
|
mm
|
No/mm
|
mm
|
kg/km
|
A
|
6.35/11kV
|
|||||||
3x35
|
6.9
|
3.4
|
1.2
|
7/4.75
|
52.4
|
1370
|
185
|
3x50
|
8.1
|
3.4
|
1.2
|
7/4.75
|
54.6
|
1530
|
225
|
3x70
|
9.7
|
3.4
|
1.2
|
7/4.75
|
57.8
|
1790
|
280
|
3x95
|
11.4
|
3.4
|
1.2
|
7/4.75
|
61.3
|
2100
|
345
|
3x120
|
12.8
|
3.4
|
1.2
|
19/3.50
|
67.3
|
2540
|
405
|
3x150
|
14.2
|
3.4
|
1.2
|
19/3.50
|
70.1
|
2840
|
460
|
3x185
|
15.7
|
3.4
|
1.2
|
19/3.50
|
73.1
|
3190
|
530
|
12.7/22kV
|
|||||||
3x35
|
6.9
|
5.5
|
1.2
|
7/4.75
|
61
|
1780
|
180
|
3x50
|
8.1
|
5.5
|
1.2
|
7/4.75
|
63.3
|
1970
|
220
|
3x70
|
9.7
|
5.5
|
1.2
|
7/4.75
|
66.5
|
2260
|
275
|
3x95
|
11.4
|
5.5
|
1.2
|
7/4.75
|
69.9
|
2600
|
335
|
3x120
|
12.8
|
5.5
|
1.2
|
19/3.50
|
75.9
|
3070
|
395
|
3x150
|
14.2
|
5.5
|
1.2
|
19/3.50
|
78.7
|
3390
|
450
|
3x185
|
15.7
|
5.5
|
1.2
|
19/3.50
|
81.7
|
3760
|
520
|
NF C33-226 | outer | Max DC Resist. | Max. tensile | Bending radius | Weight | |
12/20 kV | Diameter | /km | strength | (mm) | Approx. | |
Section mm' | (mm) | (daN) | (kg/km) | |||
single core cables | ||||||
50 | 29 | 0.641 | 150 | 377 | 754 | 700 |
95 | 32 | 0.32 | 285 | 416 | 832 | 950 |
150 | 32 | 0.206 | 450 | 416 | 832 | 1000 |
240 | 36.5 | 0.125 | 720 | 475 | 950 | 1400 |
400 | 42 | 0.078 | 1200 | 546 | 1092 | 1950 |
630 | 52.5 | 0.047 | 1890 | 683 | 1365 | 3100 |
1200 | 66 | 0.025 | 360o | 858 | 1716 | 5200 |
3 core bunched cables | ||||||
3x1x50 | 62.5 | 0.641 | 450 | 377 | 754 | 2100 |
3x1x95 | 69 | 0.32 | 855 | 416 | 832 | 2800 |
3x1x150 | 69 | 0.206 | 1350 | 416 | 832 | 3050 |
3x1x240 | 78.5 | 0.125 | 2160 | 475 | 950 | 4150 |
3x1x400 | 90 | 0.078 | 3600 | 546 | 1092 | 5800 |