Norminal Cross-sectional Area | mm2 | 16 * | 16 * | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
Number of Cores | 1 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | |
Minimum number of wires | 6 | 6 | 6 | 6 | 6 | 12 | 15 | 15 | 30 | 30 | |
Norminal insulation thickness | mm | 1.0 | 1.0 | 1.2 | 1.2 | 1.4 | 1.4 | 1.6 | 1.6 | 1.8 | 2.0 |
Diameter of insulated core | mm | 6.8 | 6.8 | 8.5 | 9.5 | 11.2 | 13.0 | 15.1 | 16.6 | 18.4 | 20.6 |
Max. dc resistance at 20°C | Ohm/km | 1.91 | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | 0.164 |
Current rating at still wind, ambient temperature = 30°C, conductor temperature = 75°C |
% | 61 | 61 | 84 | 104 | 129 | 167 | 209 | 246 | 283 | 332 |
Norminal Cross-sectional Area | mm2 | 25 | 25 | 25 | 25 | 35 | 50 | 70 | 70 | 95 | 120 |
Minimum number of wires | 6 | 6 | 6 | 6 | 6 | 6 | 12 | 12 | 15 | 15 | |
Norminal insulation thickness | mm | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.4 | 1.4 | 1.4 | 1.6 | 1.6 |
Diameter of insulated core | mm | 8.5 | 8.5 | 8.5 | 8.5 | 9.5 | 11.2 | 13.1 | 13.1 | 15.1 | 16.6 |
Max. dc resistance at 20°C | SLQ/OQ | 1.312 | 1.312 | 1.312 | 1.312 | 0.943 | 0.693 | 0.469 | 0.469 | 0.349 | 0.273 |
Calculated breaking load | O2 | 6.4 | 6.4 | 6.4 | 6.4 | 8.9 | 12.1 | 18.0 | 18.0 | 24.2 | 30.8 |
Approx. overall diameter | mm | 15.3 | 19.0 | 23.2 | 25.6 | 30.0 | 34.9 | 40.6 | 44.1 | 49.2 | 54.9 |
Approx. weight of cable | Kg/km | 160 | 290 | 400 | 500 | 680 | 920 | 1,270 | 1,510 | 1,870 | 2,340 |